PN1629 | Denial-of-Service Vulnerability in FactoryTalk® Transaction Manager

Severity:
High
Advisory ID:
PN1629
發佈日期:
June 13, 2023
最近更新:
June 13, 2023
Revision Number:
1.0
Known Exploited Vulnerability (KEV):
否
Corrected:
否
Workaround:
否
CVE IDs
CVE-2023-2778
摘要
Denial-of-Service Vulnerability in FactoryTalk® Transaction Manager

Revision History
Revision Number
1.0
Revision History
Version 1.0 - June 13, 2023

Affected Products

Affected Product First Known in Software Version Corrected in Software Version
FactoryTalk® Transaction Manager <=v13.10 BF29042 - Patch: Multiple issues, FactoryTalk Transaction Manager 13.00/13.10

Vulnerability Details

Rockwell Automation used the latest version of the CVSS scoring system to assess the following vulnerabilities. The security of our products is important to us as your chosen industrial automation supplier.  This anomaly was found internally during routine testing and is being reported based on our commitment to customer transparency and to improve their business or production environments.

CVE-2023-2778 IMPACT
A denial-of-service (DoS) vulnerability exists in the affected products. This vulnerability can be exploited by sending a modified packet to port 400. If exploited, the application could potentially crash or experience a high CPU or memory usage condition, causing intermittent application functionality issues. The application would need to be restarted to recover from the DoS.

CVSS Base Score 7.5
CVSS Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
CWE: CWE-400 Uncontrolled Resource Consumption


Known Exploited Vulnerability (KEV) database: No

Customers can use Stakeholder-Specific Vulnerability Categorization to generate more environment specific prioritization.

Risk Mitigation & User Action

Customers using the affected software are encouraged to apply the risk mitigations below, if possible. Additionally, we encourage our customers to implement our suggested security best practices to minimize the risk of the vulnerability.
  • Customers should follow the instructions in BF29042 - Patch: Multiple issues, FactoryTalk Transaction Manager 13.00/13.10 to install the patch to mitigate the issue.
  • QA43240 - Recommended Security Guidelines from Rockwell Automation

Additional Resources

  • CVE-2023-2778 JSON

Rockwell Automation Home
Copyright ©2022 Rockwell Automation, Inc.
  1. Chevron LeftChevron Left 台灣, 中國 Chevron RightChevron Right
  2. Chevron LeftChevron Left Trust Center Chevron RightChevron Right
  3. Chevron LeftChevron Left Industrial Security Adv Chevron RightChevron Right
  4. Chevron LeftChevron Left Industrial Security Advisory Detail Chevron RightChevron Right
請更新您的 cookie 設定以繼續.
此功能需要 cookie 來改善您的體驗。請更新您的設定以允許這些 cookie:
  • 社群媒體Cookie
  • 功能Cookie
  • 性能Cookie
  • 行銷Cookie
  • 全部Cookie
您可以隨時更新您的設定。想了解更多訊息,請參閱我們的 {0} 隱私政策
CloseClose