PN1597 | MicroLogix 1400/1100 Vulnerable to Clickjacking Vulnerability

Severity:
Medium
Advisory ID:
PN1597
게시한 날짜:
July 07, 2022
최근 업데이트:
July 07, 2022
Revision Number:
1.0
Known Exploited Vulnerability (KEV):
아니요
Corrected:
아니요
Workaround:
아니요
CVE IDs
CVE-2022-2179
요약
MicroLogix 1400/1100 Vulnerable to Clickjacking Vulnerability

Revision History
Revision History
Version 1.0 – July 7, 2022

Executive Summary

Rockwell Automation received a vulnerability report from Pawan V. Sable and Pranita Sadgir, and Dr. Faruk Kazi of COE-CNDS from Veermata Jijabai Technological Institute (VJTI) India. If exploited, this vulnerability could potentially have a high impact on the confidentiality of the targeted device.

Customers using affected versions of this software are encouraged to evaluate the mitigations provided below and apply them where appropriate. Additional details relating to the discovered vulnerability, including the products in scope, impact, and recommended countermeasures, are provided herein. We have not received any notice of this vulnerability being exploited in Rockwell Automation products.

Affected Products

  • MicroLogix™ 1400 v. 21.007 and below
  • MicroLogix™ 1100 all versions

Vulnerability Details

Rockwell Automation was made aware that the X-Frame-Options header is not configured in the HTTP response and allows potential clickjacking attacks. Exploitation of this vulnerability could potentially allow a malicious user to trick a legitimate user into using an untrusted website. If exploited, this vulnerability could lead to a loss of sensitive information, such as authentication credentials.

(CVE 2022 - 2179) MicroLogix Controllers Vulnerable to Clickjacking Attack
CVSS Base Score: 6.5 /10 (Medium)
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N

Risk Mitigation & User Action

Customers using the affected software are encouraged to implement the risk mitigations below to minimize the risk of vulnerability. Additionally, we encourage customers to combine the risk mitigations with security best practices, also provided below, to deploy a defense-in-depth strategy.
  • Disable the web server, if possible (This component is an optional feature and disabling it will not disrupt the intended use of the device)
  • Configure firewalls to disallow network communication through HTTP/Port 80
If applying the mitigations noted above are not possible, please see our Knowledgebase article QA43240 - Security Best Practices, for additional recommendations to maintain the security posture of your environment.

References

  • CVE-2022-2179

Rockwell Automation Home
Copyright ©2022 Rockwell Automation, Inc.
  1. Chevron LeftChevron Left Rockwell Automation 홈 Chevron RightChevron Right
  2. Chevron LeftChevron Left Trust Center Chevron RightChevron Right
  3. Chevron LeftChevron Left Industrial Security Adv Chevron RightChevron Right
  4. Chevron LeftChevron Left Industrial Security Advisory Detail Chevron RightChevron Right
계속 진행하기 위해 쿠키 설정을 업데이트하십시오..
この機能には、お客様の利便性を向上させるためにクッキーが必要です。これらのクッキーを許可するように設定を更新してください:
  • 소셜 미디어 쿠키
  • 기능 쿠키
  • 성능 쿠키
  • 마케팅 쿠키
  • 모든 쿠키
귀하는 쿠키 설정을 언제든지 변경할 수 있습니다. 자세한 내용은 이곳에서 확인하십시오. {0} 개인 정보 보호 정책
CloseClose