Loading

FactoryTalk® View Site Edition Multiple Vulnerabilities

Severity:
High
Advisory ID:
SD1720
公開日:
January 28, 2025
最終更新日:
January 28, 2025
Revision Number:
1.0
Known Exploited Vulnerability (KEV):
いいえ
Corrected:
はい
Workaround:
はい
CVE IDs
CVE-2025-24481,
CVE-2025-24482
ダウンロード
The following link(s) provide the security advisory in Vulnerability Exploitability Exchange format:
JSON
JSON
概要

AFFECTED PRODUCTS AND SOLUTION

Affected Product

CVE

Affected Version(s)

Corrected in Software Version

FactoryTalk® View SE

CVE-2025-24481

< V15.0

V15.0, and patch for v14 (AID 1152306)

CVE-2025-24482

< V15.0

V15.0, and patches for V12, V13, V14 (1152304)

VULNERABILITY DETAILS

Rockwell Automation used the latest version of the CVSS scoring system to assess the following vulnerabilities.

CVE-2025-24481 IMPACT

An Incorrect Permission Assignment Vulnerability exists in the product and version listed above. The vulnerability is due to incorrect permissions being assigned to the remote debugger port and can allow for unauthenticated access to the system configuration.

CVSS 3.1 Base Score: 7.3
CVSS 3.1 Vector: CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:H

CVSS 4.0 Base Score: 7.0
CVSS 4.0 Vector: CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:L/VI:L/VA:H/SC:N/SI:N/SA:N

CWE-732:  Incorrect Permission Assignment for Critical Resource
Known Exploited Vulnerability (KEV) database: No

CVE-2025-24482 IMPACT

A Local Code Injection Vulnerability exists in the product and version listed above. The vulnerability is due to incorrect default permissions and allows for DLLs to be executed with higher level permissions.

CVSS 3.1 Base Score: 7.3
CVSS 3.1 Vector: CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:H

CVSS 4.0 Base Score: 7.0
CVSS 4.0 Vector: CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:L/VI:L/VA:H/SC:N/SI:N/SA:N

CWE-94: Improper Control of Generation of Code ('Code Injection')
Known Exploited Vulnerability (KEV) database: No

Mitigations and Workarounds
Customers using the affected software are encouraged to apply the risk mitigations, if possible.

·         For CVE-2025-24481:

·         Upgrade to V15 or apply patch. Answer ID 1152306

·         Protect physical access to the workstation

·         Restrict access to port 8091 at the network or workstation

·         For CVE-2025-24482:

·         Upgrade to V15 or apply patch. Answer ID 1152304.

·         Check the environment variables (PATH), and make sure FactoryTalk® View SE installation path (C:\Program Files (x86)\Common Files\Rockwell) is before all others

For information on how to mitigate Security Risks on industrial automation control systems, we encourage customers to implement our suggested security best practices to minimize the risk of the vulnerability.

Customers can use Stakeholder-Specific Vulnerability Categorization to generate more environment-specific prioritization.

Rockwell Automation Home
Copyright ©2022 Rockwell Automation, Inc.
  1. Chevron LeftChevron Left ロックウェル・オートメーションのホーム Chevron RightChevron Right
  2. Chevron LeftChevron Left Trust & Security Chevron RightChevron Right
  3. Chevron LeftChevron Left Industrial Security Adv Chevron RightChevron Right
  4. Chevron LeftChevron Left Industrial Security Advisory Detail Chevron RightChevron Right
を続行するには、クッキーの設定を更新してください.
この機能には、お客様の利便性を向上させるためにクッキーが必要です。これらのクッキーを許可するように設定を更新してください:
  • ソーシャルメディア・クッキー
  • 機能性クッキー
  • パフォーマンスクッキー
  • マーケティングクッキー
  • 全てのクッキー
いつでも設定を更新することができます。詳しくは{0}をご覧ください プライバシーポリシー
CloseClose