Loading

FactoryTalk® Historian SE vulnerable to AVEVA-2024-001 and AVEVA-2024-002

Severity:
High
Advisory ID:
SD1669
公開日:
May 06, 2024
最終更新日:
November 19, 2024
Revision Number:
1.0
Known Exploited Vulnerability (KEV):
いいえ
Corrected:
はい
Workaround:
いいえ
CVE IDs
CVE-2023-31274,
CVE-2023-34348
ダウンロード
The following link(s) provide the security advisory in Vulnerability Exploitability Exchange format:
JSON
JSON
概要
FactoryTalk® Historian SE vulnerable to AVEVA-2024-001 and AVEVA-2024-002

Published Date: May 9, 2024

Last updated: May 9, 2024

Revision Number: 1.0

CVSS Score: v3.1: 7.5/10, v4.0: 7.7/10

 

 

AFFECTED PRODUCTS AND SOLUTION

 

 

Affected Product

 

 

 

 

Affected Versions

 

 

 

 

Corrected in software version

 

 

 

 

FactoryTalk® Historian SE

 

 

 

 

< v9.0

 

 

 

 

v9.01 and later

 

 

 

VULNERABILITY DETAILS

Rockwell Automation used version 3.1 and 4.0 of the CVSS scoring system to assess the following vulnerabilities. 

CVE-2023-31274 IMPACT

FactoryTalk® Historian SE utilizes the AVEVA PI Server, which contains a vulnerability, which could allow an unauthenticated user to cause a partial denial-of-service condition in the PI Message Subsystem of a PI Server by consuming available memory. This vulnerability exists in FactoryTalk® Historian SE versions 9.0 and earlier. Exploitation of this vulnerability could cause FactoryTalk® Historian SE to become unavailable, requiring a power cycle to recover it. 

CVSS Base Score v3.1: 7.5/10

CVSS Vector String: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

 

CVSS Base Score v4.0: 7.7/10

CVSS Vector String: CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:N/SC:N/SI:N/SA:H

CWE: Dependency on Vulnerable third-party Component

 

CVE-2023-34348 IMPACT

FactoryTalk® Historian SE use the AVEVA PI Server, which contains a vulnerability that could allow an unauthenticated user to remotely crash the PI Message Subsystem of a PI Server, resulting in a denial-of-service condition. This vulnerability exists in FactoryTalk® Historian SE versions 9.0 and earlier.  Exploitation of this vulnerability could cause FactoryTalk® Historian SE to become unavailable, requiring a power cycle to recover it.

CVSS Base Score v3.1: 7.5/10

CVSS Vector String: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

 

CVSS Base Score v4.0: 7.7/10

CVSS Vector String: CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:N/SC:N/SI:N/SA:H

CWE: Dependency on Vulnerable third-party Component

 

Known Exploited Vulnerability (KEV) database:  No

 

Users can use Stakeholder-Specific Vulnerability Categorization to generate more environment-specific prioritization.

 

Mitigations and Workarounds 

Users using the affected software are encouraged to install FactoryTalk® Historian SE version 9.01 or higher as soon as feasible. For customers unable to upgrade to v9.0, defensive measures are available in the Rockwell article.  

  • https://idp.rockwellautomation.com/adfs/ls/idpinitiatedsignon.aspx?RelayState=RPID%3Drockwellautomation.custhelp.com%26RelayState%3Danswers%2Fanswer_view%2Fa_id%2F1150873

Additionally, we encourage customers to implement our suggested security best practices to minimize the risk of vulnerability.  

  • Security Best Practices 

 

 ADDITIONAL RESOURCES

  • JSON CVE-2023-31274

  • JSON CVE-2023-34348

 

Rockwell Automation Home
Copyright ©2022 Rockwell Automation, Inc.
  1. Chevron LeftChevron Left ロックウェル・オートメーションのホーム Chevron RightChevron Right
  2. Chevron LeftChevron Left Trust & Security Chevron RightChevron Right
  3. Chevron LeftChevron Left Industrial Security Adv Chevron RightChevron Right
  4. Chevron LeftChevron Left Industrial Security Advisory Detail Chevron RightChevron Right
を続行するには、クッキーの設定を更新してください.
この機能には、お客様の利便性を向上させるためにクッキーが必要です。これらのクッキーを許可するように設定を更新してください:
  • ソーシャルメディア・クッキー
  • 機能性クッキー
  • パフォーマンスクッキー
  • マーケティングクッキー
  • 全てのクッキー
いつでも設定を更新することができます。詳しくは{0}をご覧ください プライバシーポリシー
CloseClose