Loading

FactoryTalk View ME Remote Code Execution Vulnerability via Project Save Path

Severity:
High
Advisory ID:
SD1709
Date de publication:
November 12, 2024
Date de la dernière mise à jour:
November 12, 2024
Revision Number:
1.0
Known Exploited Vulnerability (KEV):
Non
Corrected:
Oui
Workaround:
Oui
CVE IDs
CVE-2024-37365
Téléchargements
The following link(s) provide the security advisory in Vulnerability Exploitability Exchange format:
CVE-2024-37365
Résumé

Published Date: November 12th, 2024

Last updated: November 12th, 2024

Revision Number: 1.0

CVSS Score: v3.1: 7.3/10, v4.0: 7.0/10

The security of our products is important to us as your chosen industrial automation supplier.  This anomaly was found internally during routine testing and is being reported based on our commitment to customer transparency and to improve our customer’s business or production environments.

AFFECTED PRODUCTS AND SOLUTION

Affected Product

First Known in Software Revision

Corrected in Software Revision

FactoryTalk View ME

>= V14; when using default folders privileges

V15

 

Mitigations and Workarounds

Users using the affected software, who are not able to upgrade to one of the corrected versions, are encouraged to apply security best practices, where possible.   

·         To enhance security and prevent unauthorized modifications to HMI project files, harden the Windows OS by removing the INTERACTIVE group from the folder’s security properties.

·         Add specific users or user groups and assign their permissions to this folder using the least privileges principle. Users with read-only permission can still test run and run the FactoryTalk View ME Station.

·         Guidance can be found in FactoryTalk View ME v14 Help topic: “HMI projects folder settings”. It can be opened through FactoryTalk View ME Studio menu “help\Contents\FactoryTalk View ME Help\Create a Machine Edition application->Open applications->HMI project folder settings”.   Security Best Practices

VULNERABILITY DETAILS

Rockwell Automation used version 3.1 and 4.0 of the CVSS scoring system to assess the following vulnerabilities.

CVE-2024-37365 IMPACT

A remote code execution vulnerability exists in the affected product. The vulnerability allows users to save projects within the public directory allowing anyone with local access to modify and/or delete files. Additionally, a malicious user could potentially leverage this vulnerability to escalate their privileges by changing the macro to execute arbitrary code.

CVSS 3.1 Base Score: 7.3/10 

CVSS Vector: CVSS: CVSS:3.0/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H

CVSS 4.0 Base Score: 7.0/10

CVSS Vector: CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N

CWE-20: Improper Input Validation

Known Exploited Vulnerability (KEV) database: No

Customers can use Stakeholder-Specific Vulnerability Categorization

to generate more environment specific prioritization.

 ADDITIONAL RESOURCES

The following link provides CVE information in Vulnerability Exploitability Exchange (VEX) format, which is machine readable and can be used to automate vulnerability management and tracking activities.    

Rockwell Automation Home
Copyright ©2022 Rockwell Automation, Inc.
  1. Chevron LeftChevron Left Ûníîtééd Kíîngdòóm Chevron RightChevron Right
  2. Chevron LeftChevron Left Trust Center Chevron RightChevron Right
  3. Chevron LeftChevron Left Industrial Security Adv Chevron RightChevron Right
  4. Chevron LeftChevron Left Industrial Security Advisory Detail Chevron RightChevron Right
Veuillez mettre à jour vos préférences en matière de cookies pour continuer.
Cette fonctionnalité nécessite des cookies pour améliorer votre expérience. Veuillez mettre à jour vos préférences pour autoriser ces cookies:
  • Cookies de réseaux sociaux
  • Cookies fonctionnels
  • Cookies de performances
  • Cookies marketing
  • Tous les cookies
Vous pouvez mettre à jour vos préférences à tout moment. Pour plus d'informations, veuillez consulter notre politique de confidentialité
CloseClose