Loading

FactoryTalk® AssetCentre Multiple Vulnerabilities

Severity:
High,
Critical
Advisory ID:
SD1721
Published Date:
January 29, 2025
Last Updated:
January 29, 2025
Revision Number:
1.0
Known Exploited Vulnerability (KEV):
No
Corrected:
Yes
Workaround:
Yes
CVE IDs
CVE-2025-0477 ,
CVE-2025-0497,
CVE-2025-0498
Downloads
The following link(s) provide the security advisory in Vulnerability Exploitability Exchange format:
CVE-2025-0477
CVE-2025-0497
CVE-2025-0498
Summary

AFFECTED PRODUCTS AND SOLUTION

Affected Product

CVE

Affected Versions

Corrected Version

FactoryTalk® AssetCentre

CVE-2025-0477

All prior to V15.00.001


V15.00.01 and later

CVE-2025-0497

V11, V12, and V13 (patch available)

V15.00.01 and later

CVE-2025-0498


V11, V12, and V13 (patch available)

V15.00.01 and later

 

Mitigations and Workarounds
Customers using the affected software are encouraged to apply the risk mitigations, if possible.

For CVE-2025-0477:

o   Update FactoryTalk® AssetCentre to v15.00.01 or later.

o   The encrypted data is stored in a table in the database. Control access to the database by non-essential users.

For CVE-2025-0497

o   Update FactoryTalk® AssetCentre to v15.00.01 or later.

o   Apply patches to correct legacy versions:

§  To apply the patch for LogCleanUp or ArchiveLogCleanUp download and install the Rockwell Automation January 2025 Monthly Patch rollup, or later

§  To apply patches for EventLogAttachmentExtractor or ArchiveExtractor, locate the article BF31148

, download the patch files and follow the instructions.

o   Restrict physical access to the machine to authorized users.

For CVE-2025-0498

o   Update FactoryTalk® AssetCentre to v15.00.01 or later.

o   Apply patches to correct legacy versions:

§  To apply the patch for download and install the Rockwell Automation January 2025 Monthly Patch rollup, or later

o   Restrict physical access to the machine to authorized users.

For information on how to mitigate Security Risks on industrial automation control systems, we encourage customers to implement our suggested security best practices

to minimize the risk of the vulnerability.

Customers can use Stakeholder-Specific Vulnerability Categorization

to generate more environment-specific prioritization.

VULNERABILITY DETAILS

CVE-2025-0477 and CVE-2025-0497 reported to Rockwell Automation by Nestlé - Alban Avdiji. CVE-2025-0498 was found internally by Rockwell Automation during routine testing. Rockwell Automation used the latest version of the CVSS scoring system to assess the following vulnerabilities.

CVE-2025-0477 IMPACT

An encryption vulnerability exists in all versions prior to V15.00.001 of FactoryTalk® AssetCentre. The vulnerability exists due to a weak encryption methodology and could allow a threat actor to extract passwords belonging to other users of the application.

CVSS 3.1 Base Score: 9.8
CVSS 3.1 Vector: CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

CVSS 4.0 Base Score: 9.3
CVSS 4.0 Vector: CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N

CWE-326: Inadequate Encryption Strength
Known Exploited Vulnerability (KEV) database: No

CVE-2025-0497 IMPACT

A data exposure vulnerability exists in all versions prior to V15.00.001 of FactoryTalk® AssetCentre. The vulnerability exists due to storing credentials in the configuration file of EventLogAttachmentExtractor, ArchiveExtractor, LogCleanUp, or ArchiveLogCleanUp packages.

CVSS 3.1 Base Score: 7.0
CVSS 3.1 Vector: CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H

CVSS 4.0 Base Score: 7.3
CVSS 4.0 Vector: CVSS:4.0/AV:L/AC:H/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N

CWE-522: Insufficiently Protected Credentials
Known Exploited Vulnerability (KEV) database: No

CVE-2025-0498 IMPACT

A data exposure vulnerability exists in all versions prior to V15.00.001 of FactoryTalk® AssetCentre. The vulnerability exists due to insecure storage of FactoryTalk® Security user tokens, which could allow a threat actor to steal a token and, impersonate another user.

CVSS 3.1 Base Score: 7.8
CVSS 3.1 Vector: CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

CVSS 4.0 Base Score: 7.0
CVSS 4.0 Vector: CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N

CWE-522: Insufficiently Protected Credentials
Known Exploited Vulnerability (KEV) database: No

Rockwell Automation Home
Copyright ©2022 Rockwell Automation, Inc.
  1. Chevron LeftChevron Left United Kingdom Chevron RightChevron Right
  2. Chevron LeftChevron Left Trust Center Chevron RightChevron Right
  3. Chevron LeftChevron Left Industrial Security Adv Chevron RightChevron Right
  4. Chevron LeftChevron Left Industrial Security Advisory Detail Chevron RightChevron Right
Please update your cookie preferences to continue.
This feature requires cookies to enhance your experience. Please update your preferences to allow for these cookies:
  • Social Media Cookies
  • Functional Cookies
  • Performance Cookies
  • Marketing Cookies
  • All Cookies
You can update your preferences at any time. For more information please see our Privacy Policy
CloseClose